Temporary Diesel Generator installation with Diesel oil storage tank shall follow the EHS requirements. No such unit(s) is permitted without prior approval from EHS-Trakhees- PCFC.
41.1 Installation of the generator should not carry out without the presence of a qualified engineer.
41.2 Generator set should be enclosed housing for suppression of noise & exposure of rotating / electrical parts.
41.3 Fuel Type - Only less than .005% sulphur content fuels are permitted.
41.4 Generators shall be placed (not in setback distance) with a minimum clearance of 1.2 mts. all around and fixed on stable ground ensuring the same does not move /tilt during the operations.
41.5 There shall be accessed only by authorized personnel and relevant signs to be placed.
41.6 Proper vents should be provided to prevent accumulation of smoke/gases/CO at ground levels. Noise levels and personal protection shall be in compliance with Health & Safety Rules & Regulations.
41.7 Fuel drums (if any) and diesel tank shall be placed in a secured/impervious area at a minimum distance of 1.2 meters from the generators.
41.8 Pr...