(lonizing radiation spreads through space like light or heat. Generally, the farther you are from a source of radiation the lower your dose rate. Distance is very useful for protection when handling physically small sources. The dose rate from a small source is inversely proportional to the square of the distance from the source. This "inverse square law" means, for example, that if the distance from the source is doubled, the dose rate will be one fourth. If you get too close to a source, the dose rate can increase substantially. The dose rate at 0.1 inch from a small source will be 10,000 times higher than 10 inches from the source. lonizing radiation imparts energy to living cells. In large enough doses, this energy can damage cellular structures, such as chromosomes and membranes. If not repaired, this damage can kill the cell or impair its ability to function normally. Whether this damage is harmful depends on many factors, including the type of cell, the absorbed dose and the rate of absorption. The top management must set up a written Radiation Safety Policy. This policy must be posted on conspicuous place.)
Individuals and populations exposed to high doses of radiation display various types of detrimental effects. Examples are erythema(reddening of the skin), epillation (loss of hair), cataracts and "acute radiation syndrome."
The following methods can reduce exposure by increasing the distance between the operator and the source:
- Avoid direct handling of sources of penetrating radiation. Never directly handle unshielded multi-millicurie sources.
- Use forceps, tongs, custom-designed holders and spacers to maintain distance between your hand and the source.
- Design simple tools for securely handling sources (eg, a Lucite block with cylindrical holes to hold a vial).
- Routinely store sources at the back of benches and ventilated enclosures remote from normal access.
- Time, distance and shielding are the critical elements that must be controlled to ensure the protection of people who work with radioactive material that emit penetrating radiation.
- Use of PPE should be as per clause 26.6 mentioned below.
- The radiography bunker should have the concrete casing of 1meter with the shielding material to arrest any outside exposure of radiation. The different methods to use the shielding material are explained below in detail in a separate paragraph.
- Warning signs & danger signs are to be displayed at adequate locations & the area should be restricted for any unauthorized movement of personnel.
- The bunker should have a red warning light on the door & should be kept on whenever the radiography operation is on.
- The bunker should be minimum at the distance of 10 meters from any other process/activity in the facility.
- There is a variety of shielding materials that shall be placed between you and the source to absorb most of the radiation and effectively reduce the intensity of radiation and in some cases eliminate it that would otherwise reach you.
- The choice of shielding material shall depend on the type of radiation and other functions served by the shields (such as containment, transparency or structural support). Lead, concrete, aluminum, water and plastic are examples of commonly-used shielding materials.
- Beta rays are less penetrating than other rays, hence pure beta ray emitters can be effectively shielded by lighter materials such as glass, water or Lucite.
- When high energy beta rays are emitted and absorbed, secondary radiation is generated. The intensity of this secondary radiation increases if the beta rays are absorbed in high-atomic- number shielding material. This secondary radiation is more penetrating than the beta rays. When large quantities (ie. Greater than 100 mCi, or 3.7 GBq) of a pure beta emitter like 32P are used, the quantity of secondary radiation may be excessive unless shielded. The best shielding configuration in this case is touse, a 1/2-inch-thick Lucite acrylic sheet, or similar material, adjacent to the 32P to absorb the beta rays, while minimizing the creation of secondary radiation. Use sheets of lead foil outside the shields of Lucite to absorb the more penetrating secondary radiation like bremsstrahlung and x-rays.
- When planning an operation, calculate the shielding needs using hall-value layers and gamma- ray constants or dose-rate measurements.
- Check the adequacy of shields in all directions accessible to personnel by monitoring around (and especially beneath and behind) the operation.
- Store radioactive materials emitting penetrating radiation in lead containers with lead lids.
- Where space permits, concrete blocks may be used to enclose a radioactive storage area.
- Use mirrors, periscopes or transparent shields-for example, lead glass windows- to view operations. Avoid direct viewing by peering around shadow shields.
- Use a rigid frame to secure potentially-unstable shielding materials.
- Use custorr-designed shields for syringe barrels when millicurie quantities are being handled.
- Avoid direct exposure to high-energy, beta-emitting sources. The dose rate to the skin from beta rays is 10 to100 times as high as for gamma rays of the same energy and intensity.
- Whenever practical, use dilute solutions of high energy beta-emitting radionuclide's since the larger volume of liquid will effectively absorb more of the beta rays.
The main objective of controlling radioactive contamination is to prevent internal doses to workers. The primary means of contamination control is to prevent it by containing the radioactive materials during all handling phases. Radioactive contamination can enter the body by ingestion, inhalation or absorption through intact or damaged skin. To prevent internal exposure, it is necessary to intercept each of these contamination routes.
In areas where unsealed radioactive materials are handled, do not eat, drink, smoke, apply cosmetics, pipette by mouth or place fingers, pens and pencils in your mouth. Physical barriers can prevent accidental ingestion due to explosion or splashing.
Inhalation intakes shall be prevented by ensuring that radioactive materials are secured in sealed containers. Suitable containers include NENSure™ vials, crimp-sealed vials, flame-sealed ampules or vacuum systems and vessels vented through traps or filters. When sealed systems are impractical or additional precautions are necessary, radioactive materials that could become airborne should be handled in ventilated enclosures, such as fume hoods. Fume hoods provide protection by drawing air past the worker into an enclosure and safely exhausting it. In this process, small releases are diluted to negligible concentrations by the air flow.
- Minimize the area of the window opening to maintain an air flow velocity of about 100 linear feet per minute. Avoid excessive velocities at the face of the fume hood in order to prevent turbulence.
- Check the fume hood for proper function before use. Adequate air flow can be indicated by a paper vane suspended from the upper edge of a window opening,
- Keep your head out of the fume hood and keep the sash in the closed position when processing radioactive materials.
- Keep equipment and operations toward the rear of the fume hood to avoid impeding the flow of air through the window.
Protective clothing must be worn at all times. It must be worn properly, it must be the right fit and it must be in good condition.
- Any time you are in an area where unsealed sources of radioactive material are being used, wear a lab coat.
- A lab coat, properly fastened, will protect against casual contamination. However, it is not effective against spills or splashing and it does not protect your head, neck, hands or feet.
- Disposable lab coats are best for working around long-lived radionuclide's.
- Reusable lab coats are acceptable when handling short-lived radionuclide's, provided they are stored for a sufficient time to permit decay of any contamination prior to being washed.
- Both cloth and disposable lab coats may be reused if they are free from contamination and in good condition. They should be stored in a controlled area and you should monitor lab coats both during operations and after removing them.
- Particular attention should be paid to the sleeves, pockets and lower front surfaces of the coat.
- All lab coats should be fire-resistant. Waterproof aprons, full-body jumpsuits and hoods provide additional protection in environments where the potential for more severe contamination is present.
- Whenever your hands are near unsealed radioactive material, you should wear gloves, Gloves are secondary protection only. They should not be used to handle radioactive materials directly.
- When you no longer need gloves, they should be carefully removed, monitored and disposed or stored appropriately.
- Rips or holes make gloves ineffective. Be careful working around hot surfaces, sharp objects or chemicals that can attack the glove material.
- Periodic changes of gloves are recommended. The greater the potential hazard, the more frequent a change of gloves is needed.
- Wearing two pair of gloves and frequently changing the outer pair is also a good safety practice.
- Gloves should be monitored frequently.
- Don't use contaminated gloves or gloves that may be contaminated.
- If you are wearing gloves and they are exposed to radionuclide's that emit penetrating radiation, remove the gloves as quickly as possible to minimize skin exposure. This is particularly important when handling high-energy beta emitters.
- Don't wear sandals or open-toe shoes.
- Comfortable, sturdy footwear should be selected that will protect against contamination or injury due to broken glass or corrosive materials. In some cases, steel-toed shoes may be desirable to protect against physical hazards.
- In controlled areas where low-level floor contamination is a potential hazard, a separate pair of work shoes for use only in that area should be used.
- Safety glasses provide protection for your eyes and face; however, remember that this is secondary protection only.
- Safety glasses are of some use in protecting against low-penetration radiation, such as low- energy >-rays and medium-energy beta particles but provide little protection from penetrating gamma radiation.
- Is a must for operations that create radioactive dust, vapor or gases.
- Vented enclosures with protective filters are available for such operations.
- Use of respiratory protection devices in lieu of such primary controls is not advisable. In cases where entering a contaminated zone is unavoidable or in emergency situations, respiratory protection may be necessary.
- It may also be useful for certain decontamination operations.
- If you wish to use respiratory protection, you first must have a medical examination. Also, you must be trained in the proper...