PCFC-Entity (Business Unit) Name: Trakhees Ports, Customs & Free Zone Corporation
Department Name: Civil Engineering Department (CED)
Section Name: Permits Section (Facilities)
Document Reference Number: PCFC-TRK-CED-PS-REG-12
Revision Number: 02
Revision Date: May 2019
Classification: Public
17.1 Racking should be set up, operated and maintained according to the design, installation and operational guidelines of the racking manufacturer. It should be designed specifically for the size, shape and weight of the products being stored. Any modification should be checked by the original supplier/manufacturer/ designer prior to installation implementation in the facility.
17.2 Bottom portions of frames exposed to possible collisions by forklifts or other moving equipment should be fitted with upright protectors and end of rack protectors.
17.3 Racking should be inspected frequently for damage and overloading and at least annually to check its integrity.
17.4 The height-to-depth ratio of a storage rack shall not exceed 3 meters to 1 meter measured to the topmost beam position, unless the rack is anchored or braced externally to resist a...