Version 0
Federal Authority for Nuclear Regulation (FANR), 2012 P O Box 112021, Abu Dhabi, United Arab Emirates [email protected]
Regulatory Guides are issued to describe methods and/or criteria acceptable to the Authority for meeting and implementing specific requirements in the Authority's regulations. Regulatory Guides are not substitutes for regulations, and compliance with them is not required. Methods of complying with the requirements in regulations different from the guidance set forth by the Regulatory Guide can be acceptable if the alternatives provide assurance that the requirements are met.
For the purposes of this Regulatory Guide the following terms shall have the meaning set forth below. Other capitalised terms used but not defined herein shall have the meaning ascribed to them in Article 1 of the Federal Decree-Law No. 6 of 2009 Concerning the Peaceful Uses of Nuclear Energy (the Law):
Access Control: The element of a physical protection system designed to increase adversary penetration time for entry into and/or exit from the Nuclear Facility or transport or limiting entry to a computer network. Access control/delay can be accomplished by physical barriers, activated delays, and/or personnel Authentication of identity.
Asset: Anything that has value to the organization, including:
a. People and their qualification and skills
b. Information
c. Software
d. Services
e. Equipment, such as computers
f. Intangibles, such as reputation
Authentication: Provision of assurance that a claimed characteristic of an entity is correct
Critical Digital Asset (CDA): A digital device or system that plays a role in the Operation or Maintenance of a Critical Digital System and can impact the proper functioning of a Critical Digital System.
Critical Digital System: Those systems and networks associated with Items Important-to Safety; security; safeguards, or Emergency Preparedness Functions; including onsite and offsite communications; and support systems and equipment.
Cyber Attack: The manifestation of either physical or logical (i.e., electronic or digital) threats against computers, communication systems, or networks that may:
These attacks may occur individually or in any combination.
Cyber Security: The protection of equipment, systems, and networks against attacks by individuals or organisations that would seek to cause harm, damage, or adversely affect the confidentiality, integrity, or availability of an information system or that seek to use an information control system for an unauthorised purpose that will affect the functions performed by such equipment, systems, and networks. Cyber Security provides a high assurance that digital computer, network and communication systems are adequately protected against cyber-attacks up to and including the DBT.
Cyber Security Incident: An event that actually or potentially jeopardizes the functional or performance characteristics of a digital Asset;
or
a violation of security policies or procedures.
Cyber Security Culture: The product of individual and group values, attitudes, perceptions, competencies and patterns of behaviour that determine the commitment to Nuclear Facility's Cyber Security policies, procedures and practices.
Defence-in-Depth: The combination of multiple layers of systems and measures that have to be overcome or circumvented before nuclear security is compromised.
Design Basis Threat (DBT): The largest reasonable threat against which the Licensee shall be expected to defend. It describes the attributes and characteristics of potential insider and/or external adversaries, who might attempt unauthorised removal of Nuclear Material or sabotage, against which a Physical Protection system is designed and evaluated.
Emergency Preparedness: The capability to take action that will effectively mitigate the consequences of an Emergency.
Emergency Preparedness Functions: Identified task, or set of tasks, performed by systems, equipment and individuals to provide reasonable assurance that adequate protection and mitigation measures can be taken in the event of a radiological emergency at the Nuclear Facility.
Items Important to Safety: An item that is part of a Safety Group and/or whose malfunction or failure could lead to radiation exposure of the site personnel or members of the public, including:
Limited Access Area: A designated area containing a Nuclear Facility and Nuclear Material to which access is limited and controlled for physical protection purposes.
Owner-Controlled Area: An area outside of the Protected Area but inside the site boundary.
Protected Area: An area encompassed by physical barriers and to which access is controlled; the outermost of two barriers to provide protection against unauthorized access to the Nuclear Facility.
Recovery: Steps taken to restore a system or device to its original state of operation following a catastrophic or partial loss of functionality or when an original state of operation is challenged by either an event (such as a Cyber Attack) or anomaly (behaviour not expected from Normal Operation).
Remote Access: The ability to access a Critical Digital Asset, computer, node, or network resource located within an identified defensive level from a Critical Digital Asset, computer, or node that is physically located in a less secure defensive level.
Risk (cyber risk): A combination of the likelihood of a Critical Digital Asset being potentially impaired due to a Cyber Security Incident and the consequences to the Nuclear Facility from that impairment.
Sanitation: The process of removing data from storage media, such that there is reasonable assurance that the data may not be easily retrieved and reconstructed.
Security Controls: Countermeasures employed to avoid, counteract, or minimise security risks. Management, technical, and operational controls collectively referred as Security Controls.
Security Mechanisms: A broad range of physical, logical, procedural, and technological methods with which to provide a secure physical or logical environment for devices (e.g., computing or controls hardware) or processes (e.g., firmware or software).
Supporting Function: A function that directly or indirectly supports the operation and functionality of systems that perform safety, security, safeguards and Emergency Preparedness Functions. Examples of supporting functions include heating, ventilation, air conditioning, communications, fire suppression, or any function which, if compromised, could have an adverse impact on safety, security, safeguards, or Emergency Preparedness.
Users of Digital Assets: Licensee's staff, contractors, and vendors that have access to any digital system in the Nuclear Facility.
Vulnerability: A weakness in the physical or electronic configuration of a Critical Digital Asset or connected digital Asset that could allow an action that compromises the functionality of the Asset.
This Regulatory Guide provides methods for protecting digital computers, communications systems, and networks, and an approach deemed acceptable by the Authority for complying with requirements of FANR-REG-08, Regulation on Physical Protection Including Access Controls. The information contained within this guide may be used when establishing or modifying provisions against threats to digital Assets, and it embodies the guidance provided by other organizations such as the International Electrotechnical Commission (IEC), the International Atomic Energy Agency (IAEA), the U.S. National Institute of Standards and Technology (NIST) and the U.S. Nuclear Regulatory Commission (USNRC).
The guidance in this Regulatory Guide applies to organizations applying for a Nuclear Facility limited Construction, Construction, or operating Licence as well as to Licensees currently operating Nuclear Facilities.
Digital computer and communications systems and networks performing the following categories of functions must be protected from those Cyber Security Incidents up to and including those identified in the Design Basis Threat that would act to modify, destroy, or compromise the integrity or confidentiality of data and/or software; deny access to systems, services, and/or data; and impact the operation of systems, networks, and associated equipment.
Lower-tier policies related to the use of computer systems, such as issue-specific and system-specific policies, should conform to the Cyber Security programme.
3. The Cyber Security programme should describe how a high level of assurance has been achieved that all safety, security, safeguards, and Emergency Preparedness (SSSEP) Functions are protected from cyber threats.
4. The Cyber Security programme should be part of the facility's Physical Protection Plan (PPP). The incorporation of Critical Digital Assets into the site Physical Protection Plan requires that the high assurance required for Physical Protection also is applicable to the protection of these Assets.
5. Cyber Security is a cross-cutting discipline and, as such, its provisions impact on other security domains as well as other Facility programmes. Therefore the Cyber Security programme should be developed in cooperation with Licensee staff responsible for Operations, Maintenance, security, engineering, Emergency Preparedness, safety, and information and communication technology (ICT).
6. In response to the cyber threat environment, those digital systems and Assets determined to be critical to the Operation of the Nuclear Facility should be identified. The potential consequences of a Cyber Attack on the Nuclear Facility SSSEP functions should be evaluated.
7. To leverage existing procedures, some components of a Cyber Security programme may be integrated into existing engineering –related programmes.
8. Given the dynamic nature of cyber threats and changing technological conditions, the Cyber Security programme should be periodically assessed and improved.
9. Cyber Security training should be implemented to ensure that Users of Digital Assets are educated on Nuclear Facility security policy and procedures and an adequate Cyber Security Culture is created and continually improved.
The Nuclear Facility Cyber Security programme should employ a graded approach that systematically maintains security throughout the lifecycle of the Critical Digital Assets (CDAs). In this approach, Cyber Security provisions applied to a given CDA (and its Supporting Functions when applicable) are commensurate with the CDA importance to Nuclear Safety, security, safeguards, or Emergency Preparedness.
The Nuclear Facility Cyber Security programme should include the following elements:
Roles, responsibilities, authorities, and functional relationships should be documented to ensure that they are well understood by all Users of digital Assets.
Division of responsibilities for personnel administering the Cyber Security programme should generally include the following individuals:
a) A Cyber Security programme sponsor who is a member of senior site management (executive or officer level). This individual should:
b) A Cyber Security programme officer who has expert-level knowledge of Cyber Security and familiarity-level knowledge of interfacing disciplines such as Nuclear Safety, safeguards, Emergency Preparedness and other aspects of security in Nuclear Facilities. The Cyber Security officer should be responsible for:
c) Cyber Security specialists who are responsible for:
d) A Cyber Security team consisting of individuals from several organization departments including information and communication (ICT), security, operations, engineering, Emergency Preparedness.
e) Auxiliary staff comprises organisations and individuals who operate, maintain, or design Critical Digital Systems. This includes operations personnel, engineers, technicians, users, contractors and vendor representatives.
An assessment of site specific digital computer systems, communication systems and networks should be performed to identify components that, if compromised, could have an adverse impact on safety, security, safeguards, or Emergency Preparedness Functions. This set of components constitutes the Critical Digital Assets (CDAs) that require enhanced protection against and mitigation from the consequences of Cyber Security Incidents.
Information sources to be reviewed to identify Critical Digital Systems and CDAs include, but are not limited to, the Nuclear Facility Safety Analysis Report, the site-specific Probabilistic Risk Assessment, design documentation, and documents associated with the facility's maintenance program.
A method for documenting the identification of Critical Digital Systems and CDAs should include the following:
The Cyber Security programme should be designed to apply and maintain Security Defence-in-Depth protective strategies to ensure the capability to detect, respond to, and recover from Cyber Security Incidents.
The overall site defensive strategy should employ a defensive model that defines formal communication boundaries (or security levels) where defensive measures are deployed to detect, prevent, delay, mitigate, and recover from Cyber Security Incidents. An example of such a defensive architecture is one that includes a series of concentric defensive levels of increasing security which correspond to existing physical security levels at a Nuclear Facility (e.g., Limited Access Area, Protected Area, Owner-controlled...