| GOVERNMENT OF DUBAI | Guidelines | |
| DHCR HSE Fire and Life Safety Preparedness Guidelines for the DHCC Community |
$$document-title align=center 1. INTRODUCTION $$
Health, Safety and Environment (HSE) Fire and Life Safety Preparedness Guidelines by Dubai Healthcare City Authority – Regulatory (DHCR), the regulator of the Dubai Healthcare City (DHCC) free zone, aim to provide guidance for all members of the DHCC Community in safety management to protect people and property in the free zone.
In line with the UAE Federal and local HSE requirements as well as international best practice, DHCR's HSE Department will work closely with the DHCC Community to ensure all necessary measures are in place to respond to any emergencies and to mitigate potential consequences.
DHCR's HSE Department would like to advise the DHCC Community as their HSE Oversight Community Adviser that there is a legal duty and requirement on all Business Partners (BPs) and investors - regardless of the size, activity, occupancy or hazards - to know and familiarize themselves with their statutory duties regarding fire and life safety.
Fire Door Tolerances / Fire Retardant Burn Time (Passive System) to allow sufficient time to evacuate
Door closed at the time of fire which never penetrated. NOTE: Fire Rated Door, allowing sufficient time for safe evacuation
DHCR HSE is committed to supporting the free zone's Business Partners and investors on Fire and Life Safety emergency procedures to ensure preparedness in the event of an emergency.
A recent study carried out by UK's National Health Service identified that:
Case study Before
The Service we provide
Case Study After
The Consequences
10 minutes after initial notification of fire, ward completely destroyed
All workplaces need a plan for fire emergencies, and quick and effective actions to eliminate harm.
During a fire emergency, staff are more likely to respond reliably if they:
To be prepared, an emergency plan is essential. The UAE Fire and Life Safety Code stipulates mandatory requirements - a specific emergency plan is prepared and all the occupants are informed about their role in emergency management, which may be inspected by Dubai Civil Defence (DCD) at any time, and will form part of DHCR HSE site visits.
Successful emergency evacuation of any buildings depends on prompt and correct decisions of the occupants and their immediate actions during the first few minutes of the incident. Occupants are on their own until the arrival of authorities such as Dubai Civil Defence or Dubai Police.
All staff should be consulted and informed as follows:
The updated UAE Fire and Life Safety Code will contain more detail on mandatory requirements for owners / building occupants and specify legal responsibilities in maintenance and repair work for businesses, regardless of size or activity.
The UAE Fire and Life Safety Code states that it is the responsibility of the property owner/ partner / facilities manager and any other appropriate personnel appointed for the implementation of the emergency plan and procedure.
IMP: UAE Fire and Life Safety Code puts an onus on EVERYONE.
The DHCR HSE Fire and Life Safety Preparedness Guidelines provide only a summary of what is required. Each organization is required to ensure they have the appropriate, competent adviser with sufficient training, experience and knowledge to ensure compliance with the procedures outlined below.
| Steps | Business Partners Actions | DHCR HSE Actions |
|---|---|---|
| Step 1 | Complete the DHCR HSE Questionnaire and return to DHCR HSE Department | DHCR will send the Questionnaire to the DHCC Community |
| Step 2 | Complete Fire and Life Safety Checklist and submit to DHCR HSE Department | DHCR will send the checklist to the DHCC Community |
| GOVERNMENT OF DUBAI | DHCR HSE Fire and Life SafetyPreparedness Guidelines | ||
| Document # GL/HSE/001/01 | Issue Date: 26 July 2017 | ||
| Step 4 | Ensure fire drills, conducted twice a year, are effective | |||
| Step 5 | Fire Protection and Detection Systems are effective and evidence based | |||
GOVERNMENT OF DUBAI
سلطة مدينة دبي الطبية
Dubai Healthcare City Authority
القطاع التنظيفي - Regulatory
Document # GL/HSE/001/01
Issue Date: 26 July 2017
| Safe and proper use of portable fire extinguishersMaintenance and inspection of portable fire extinguishers | ||||
| Level 2 – Mandatory | Fire Warden | The mechanics of fireFundamentals of public fire safetyClassification of firesTypes of portable fire extinguishersSafe and proper use of portable fire extinguishersMaintenance and inspection of portable fire extinguishersRoles and Responsibilities of a fire wardenUnderstand the different types of fire safety installationsEmergency escape routesConducting fire drillsWorkplace fire prevention | Six hours |
The UAE Federal Law No. 505 requires all companies to provide adequate training in fire awareness on the basics of preventive fire safety and firefighting which must be completed, every two years in order to obtain a certificate stating that preventive safety requirements are met by a recognized DCD-approved provider.
Facilities must adhere to enrolling all employees in training on preventive fire safety and firefighting as per the classifications below:
| Classification A | 10 percent of all employees must be trained on the basics of preventive fire safety and firefighting | If there is only one employee – They must be trained |
| Classification B | 50 percent of all employees must be trained on the basics of preventive fire safety and firefighting | If there are two employees |
The training will help:
Under the UAE Fire and Life Safety Code, all appointed ire wardens must be full-time staff members and should be familiar with the general operations and hazards on-site as well as the emergency procedures for their respective floors. Two fire wardens must be appointed for each of the fire areas. Two wardens are required in the event that one is unavailable. Fire Warden Training is specialist training in addition to Basic Fire Safety training.
The training will cover the following:
| GOVERNMENT OF DUBAI | DHCR HSE Fire and Life SafetyPreparedness Guidelines | ||
| Document # GL/HSE/001/01 | Issue Date: 26 July 2017 | ||
| Assist in the evacuation processRemain at the fire exit door and guide occupants out of the buildingCarry out monthly fire safety checksFamiliar with the location of emergency equipmentFire drillsA fire drill should be conducted every six months, at unexpected times, to simulate fire conditions i.e. one escape route obstructed, no advance warning given other than to involve staff for the purposes of safety.Evacuation drills must involve all occupantsEvacuation coordinator(s) and fire wardens are expected to perform their assigned duties as if in an actual emergency situationEvacuation Drill Report forms should be provided to the drill coordinators and fire wardens to make notes during the evacuation drillStaff attend the designated assembly points | |
| Step 5: Fire Protection and Detection Systems | DHCR HSE will release a Fire and Life Safety Checklist, which Business Partners should complete as a self-assessment to evaluate the program for maintenance / servicing that DHCR will be undertaking.The Fire Protection and Detection Systems guidelines are not an exhaustive list. However, each Partner should conduct a review of all equipment and identify the inspection and testing requirements. More frequent inspection / testing may be necessary where appropriate including conditions such as high frequency fire outbreaks; severe hazard; susceptibility to tampering, damage, vandalism or malicious mischief; and/or locations, which make extinguishers susceptible to mechanical injury such as exposure to abnormal temps, corrosive atmospheres or physical obstructions. |
Fire Door Wedged Open
Fire exit obstructed with waste, no escape
Fire Exit Doors Locked, No Escape
| Fire Protection and Detection Systems | |
|---|---|
| Type of Fire Systems | Maintenance / Service of Fire Systems |
GOVERNMENT OF DUBAI
سلطة مدينة دبي الطبية Dubai Healthcare City Authority Regulatory - القطاع التنظيمي
Document # GL/HSE/001/01
Issue Date: 26 July 2017
| weekly inspections for fire alarm and detection systems should be carried out on each occasion that the building is used. Quarterly and annual inspections by competent, trained person, as follows: At least one detector, call point or end of line switch on at least one zone (seek Fire Engineer for guidance on the zones) shall be operated to test the ability of the controlAll defects shall be recorded in the log book and reported to the responsible personEntries in the log bookBatteries should be examinedBatteries, including reserves, shall be testedAlarm functions of the control and equipmentNOTES:It is recommended that during the quarterly/periodic service, a percentage of the detection devices should be tested such that at the end of the annual period all devices have been tested.On completion of the work, a Certificate of Servicing/Testing shall be given to the responsible person. The certificate shall indicate its validity/expiry date.Break glass units need not be damaged for test purposes. A test key can be obtained from the supplier of the system. | |
| Sprinkler systems | Weekly tests should be delegated to a person familiar with the functions of the installation. The nominated person should receive basic training from the installer/supplier, to check: Water and air pressure gaugesWater levels |
| Water motor alarm testAutomatic pump starting testDiesel engine restarting testTrace heating and localized heating systems Monthly, the electrolyte level and density of all lead acid cells (including diesel engine starter batteries and those for control panel power supplies) shall be checked. If the density is low, the battery charger shall be checked and, if this is working normally, the battery or batteries affected shall be replaced. Quarterly, carried out by the installer/supplier, potential hazards and checks should be reviewed as per the following: Sprinklers, multiple controls and sprayersPipework and pipe supportsWater supplies and their alarmsElectrical suppliesStop valvesFlow switchesReplacement The following checks and inspection shall be made at intervals of no more than 12 months: Automatic pump flow testDiesel engine failed-to-start testFloat valves on water storage tanksPump suction chambers and strainers | |
| Sprinkler valve | Dry alarm valves - the moving parts of dry alarm valves, and any accelerators and exhausters, in dry pipe installations and subsidiary |